Ask someone what size cable is required for a circuit and you'll often hear an answer immediately.
“Use 2.5 mm².”
“Put it on 6 mm².”
“It's only 32 amps.”
But cable sizing doesn't really work like that.
A cable that can carry 32 A when clipped directly to a wall may not be suitable for the same circuit when:
buried in insulation, grouped with other cables, installed in a hot environment, run over a long distance or terminated into equipment with particular temperature limitations.
The load is only the beginning.
A proper electrical cable-sizing calculation considers the complete installation.
In the UK, this process is carried out using the requirements and guidance associated with BS 7671, with the latest edition being BS 7671:2018+A4:2026. The IET also publishes supporting guidance including the On-Site Guide and Guidance Note 1 for selection and erection. IET Wiring Regulations
This guide walks through the process.
The basic cable sizing process
A useful way to think about cable sizing is:
Load
↓
Design current — Ib
↓
Protective device — In
↓
Installation method
↓
Correction factors
↓
Required tabulated cable capacity — It
↓
Select cable size
↓
Check voltage drop
↓
Check fault protection
↓
Check CPC and thermal withstand
↓
Final cable selection
Notice something important?
Selecting the cable isn't the first step.
It's somewhere in the middle.
Step 1 — Determine the design current, Ib
The first question is:
How much current does the circuit actually need to carry?
This is known as the design current, normally represented as:
Ib
How it is calculated depends on the load.
For a basic single-phase load:
Ib = P ÷ (V × PF)
Where:
Ib = design current in amperes
P = power in watts
V = voltage
PF = power factor
For equipment such as motors, efficiency may also need to be considered.
For a three-phase balanced load:
Ib = P ÷ (√3 × V × PF)
Again, other equipment characteristics may need to be incorporated depending on the load.
Example: single-phase load
Suppose we have a 7 kW resistive load supplied at 230 V.
For a resistive load, assume a power factor close to 1 for this simplified example.
Ib = 7,000 ÷ 230
Ib ≈ 30.4 A
Our cable therefore needs to supply a design current of approximately:
30.4 A
But we still haven't selected the cable.
Step 2 — Select the protective device, In
Next comes the protective device.
Its rated current is represented by:
In
One of the fundamental relationships used when designing a circuit is:
Ib ≤ In ≤ Iz
Where:
Ib = circuit design current
In = nominal current or current setting of the protective device
Iz = current-carrying capacity of the conductor under its actual installed conditions
For our previous example:
Ib = 30.4 A
A possible protective-device rating could therefore be:
In = 32 A
At the simplest level:
30.4 A ≤ 32 A
But now we need to make sure the installed cable can safely carry the required current.
The IET's design guidance follows this principle: establish the design current first, select the protective device and then determine a conductor capable of carrying the required current under the actual installation conditions. IET Wiring Regulations
Step 3 — Identify the cable type
Before jumping to a cable-size table, we need to know what cable we're actually designing.
Examples include:
PVC insulated and sheathed cable
XLPE insulated SWA
Singles in containment
Mineral insulated cable
Fire-resistant cable
Flexible cable
Different cable constructions have different:
operating temperatures, current-carrying capacities, voltage-drop characteristics and installation requirements.
The material matters too.
Copper and aluminium conductors don't behave identically.
So “what size cable?” cannot be answered properly without knowing what type of cable.
Step 4 — Establish the installation method
This is one of the most important parts of cable sizing.
The same cable can carry different amounts of current depending on how it is installed.
For example, a cable may be:
clipped directly to a surface,
installed in conduit,
installed in trunking,
buried underground,
installed on cable tray,
run through thermal insulation,
or grouped with several other loaded cables.
Each arrangement affects the cable's ability to dissipate heat.
A cable surrounded by free air can generally lose heat more effectively than one buried inside insulating material.
That affects its current-carrying capacity.
BS 7671 therefore uses reference methods representing different installation arrangements.
The correct reference method must be established before selecting the cable from the appropriate current-carrying-capacity table.
Why heat matters
When electrical current flows through a conductor, energy is lost as heat.
The relationship can broadly be understood through:
P = I²R
Where:
P = power lost as heat
I = current
R = conductor resistance
Notice that current is squared.
That means increasing current has a significant effect on heating.
The purpose of cable-sizing requirements is therefore not simply making sure electricity reaches the equipment.
The conductor also needs to remain within an acceptable operating temperature.
The IET notes that cable current-carrying capacities, rating factors and voltage-drop values are all part of keeping cables within appropriate operating limits. IET Wiring Regulations
Step 5 — Apply correction factors
The tabulated current-carrying capacity assumes particular conditions.
Real installations often differ.
Correction or rating factors are therefore used.
Typical factors encountered during cable design include:
FactorTypical considerationCaAmbient temperatureCgGrouping of cablesCiThermal insulationCsSoil thermal resistivityCdDepth of buried cableCfParticular fuse/protection considerations where applicable
Not every factor applies to every installation.
And this is important:
Don't simply multiply every correction factor you've ever heard of into every calculation.
The correct BS 7671 method depends on the cable, protective device, installation arrangement and circumstances.
Appendix 4 of BS 7671 provides the detailed cable-sizing methodology.
Ambient temperature — Ca
Current-carrying tables assume particular ambient conditions.
If a cable is installed somewhere hotter than the table's assumed environment, it may not be able to dissipate heat as effectively.
Examples include:
plant rooms,
roof voids,
industrial environments,
areas adjacent to heat-producing equipment.
The cable may therefore require derating.
Ambient temperature can also influence protective devices, another reason thermal conditions need to be considered as part of the installation rather than just the cable itself. IET Wiring Regulations
Grouping — Cg
Imagine one loaded cable sitting by itself on a cable tray.
Now imagine twenty loaded cables tightly bunched together.
The thermal environment isn't the same.
Each cable contributes heat and neighbouring cables can make it harder for that heat to escape.
A grouping factor may therefore need to be applied.
This is particularly relevant for:
cable tray systems,
trunking,
conduit,
distribution routes,
service risers.
It's also why simply copying a cable size from a previous circuit can be dangerous.
The load may be identical.
The installation conditions may not be.
Thermal insulation — Ci
Thermal insulation is designed to prevent heat from escaping.
That's excellent for buildings.
It's potentially problematic for electrical cables.
A cable surrounded by insulation can retain significantly more heat than one installed in free air.
The designer therefore needs to understand whether the cable:
passes through insulation,
is partially surrounded by insulation,
or is fully enclosed by it for a significant distance.
Ignoring insulation can result in the selected conductor operating at an excessive temperature.
Underground cables
Buried cables introduce another group of considerations.
These can include:
soil thermal resistivity,
ground temperature,
burial depth,
grouping,
duct arrangements.
The IET notes that cable sizing in the ground depends heavily upon the assumed installation conditions and that appropriate correction factors must be applied where actual conditions differ. IET Wiring Regulations
Again:
Cable size cannot be separated from installation method.
Step 6 — Determine the required tabulated current-carrying capacity
We now need to work backwards to determine how much capacity the cable must have before the correction factors are applied.
A simplified form frequently encountered is:
It ≥ In ÷ (Ca × Cg × Ci × ...)
Where:
It = required tabulated current-carrying capacity
Let's use an illustrative example.
Suppose:
Ib = 29 A
and we select:
In = 32 A
Assume the appropriate design assessment establishes:
Ca = 0.94
and:
Cg = 0.80
These values are purely illustrative here — the designer must obtain the actual applicable factors from the current design standard.
Combined correction factor:
0.94 × 0.80 = 0.752
Therefore:
It ≥ 32 ÷ 0.752
It ≥ 42.6 A
So we don't simply look for a cable capable of carrying 32 A in the table.
We look for one with a tabulated current-carrying capacity of at least:
42.6 A
under the appropriate reference method.
This is how apparently modest loads can result in larger cables once installation conditions are considered.
Step 7 — Select a preliminary cable size
Now we consult the relevant cable table.
Suppose one candidate cable has a tabulated capacity below:
42.6 A
It fails.
The next size has a capacity above:
42.6 A
That cable may satisfy the current-carrying capacity requirement.
But we're still not finished.
This is a common beginner mistake.
“The cable carries the current, therefore the cable is correct.”
Not necessarily.
We still need to check voltage drop and fault conditions.
Step 8 — Check voltage drop
Every conductor has impedance.
As current flows through the cable, some voltage is lost along it.
That is voltage drop.
The longer the circuit becomes, the more important voltage drop usually becomes.
A common calculation using tabulated cable data is:
Vd = (mV/A/m × Ib × L) ÷ 1000
Where:
Vd = voltage drop in volts
mV/A/m = tabulated voltage-drop value
Ib = design current
L = circuit length in metres
The correct value must be selected for the cable and circuit configuration being designed.
Example voltage-drop calculation
Suppose:
Ib = 28.9 A
Circuit length:
35 m
And, purely for our worked example, assume the applicable cable table gives:
8 mV/A/m
Then:
Vd = (8 × 28.9 × 35) ÷ 1000
Vd ≈ 8.1 V
For a 400 V circuit:
8.1 ÷ 400 × 100
≈ 2.0% voltage drop
Whether that is acceptable depends on the complete installation, connected equipment and applicable design requirements.
How much voltage drop is allowed?
For low-voltage installations supplied directly from a public LV distribution system, BS 7671 guidance commonly gives recommended values of:
3% for lighting
and
5% for other uses
between the origin of the installation and the load point.
However, these are informative recommended values, and the actual requirement can depend on the equipment being supplied. The IET specifically warns designers to consider equipment operating requirements rather than treating the percentage as the only test. IET Wiring Regulations
This matters particularly with sensitive equipment.
A design can potentially sit inside a general percentage allowance while still creating operating problems for the connected equipment.
Don't use the entire voltage-drop allowance on one circuit
Suppose a final circuit is supplied from:
Main LV Switchboard
↓
Sub-main
↓
Distribution Board
↓
Final circuit
The final circuit isn't the only conductor producing voltage drop.
The sub-main does too.
For example:
Sub-main voltage drop:
1.5%
Final circuit voltage drop:
2.5%
Total:
4.0%
The designer needs to consider the voltage drop from the origin of the installation to the final load, not just whichever cable happens to be under calculation.
This is particularly important on large commercial projects.
Cable sizing becomes more important on long circuits
Consider two identical loads.
Both draw:
20 A
Circuit A is:
10 metres
Circuit B is:
150 metres
Their design currents are identical.
But the cable sizes may not be.
Why?
Because Circuit B experiences significantly greater:
voltage drop and conductor impedance.
The cable may therefore need increasing even though the load current hasn't changed.
This is why:
Cable size is not determined by amperage alone.
Step 9 — Check earth fault loop impedance
The cable now carries the current.
Voltage drop is acceptable.
Are we finished?
Still no.
The protective device must also be able to disconnect the supply quickly enough under an earth-fault condition where automatic disconnection of supply is used.
The earth fault current path includes impedances throughout the fault loop.
The earth fault loop impedance is commonly represented as:
Zs
and can conceptually be considered as:
Zs = Ze + (R1 + R2)
Where:
Ze = external earth fault loop impedance
R1 = line conductor resistance
R2 = circuit protective conductor resistance
The actual design needs to account for the applicable conditions and temperature.
Why Zs matters
Suppose a line conductor touches an exposed conductive part during a fault.
We need sufficient fault current to operate the protective device within the required time.
If the fault-loop impedance is too high:
fault current decreases.
If the fault current becomes too low:
the protective device may take too long to disconnect.
That creates a safety problem.
BS 7671 therefore gives maximum earth-fault loop impedance requirements for relevant protective devices.
The IET explains that these design values take conductor operating temperature into account, which is why measured values during testing are treated differently from design values. IET Wiring Regulations
Step 10 — Size the circuit protective conductor
The circuit protective conductor — the CPC — also needs to be appropriately sized.
Depending on the circumstances, this may be determined using the applicable BS 7671 requirements or checked using the adiabatic equation.
The familiar form is:
S = √(I²t) ÷ k
Where:
S = minimum conductor cross-sectional area
I = prospective fault current
t = protective-device operating time
k = factor dependent upon conductor and insulation materials and relevant temperatures.
The purpose is to check whether the protective conductor can withstand the thermal energy created during the fault until the protective device disconnects.
A fault may last only a fraction of a second.
But the current can be extremely high.
The conductor needs to survive it.
Step 11 — Check short-circuit withstand
The same underlying idea also applies to conductors exposed to short-circuit current.
An upstream fault may produce many thousands of amperes.
The protective device should clear that fault quickly.
But during that time the cable experiences substantial thermal stress.
The designer therefore needs to consider:
prospective short-circuit current, protective-device characteristics and conductor withstand.
This becomes particularly important near large transformers and main LV switchboards where fault levels can be much higher.
Step 12 — Check the protective device breaking capacity
Cable sizing and protective-device selection aren't completely separate activities.
Suppose a calculated prospective short-circuit current is:
12 kA
but the selected protective device can only safely interrupt:
6 kA
That's a problem.
The circuit needs a suitable protective arrangement capable of dealing with the prospective fault current.
Again, good electrical design looks at the circuit as a system:
load + cable + protective device + supply characteristics.
Not as independent components.
Step 13 — Check disconnection times
The protective device must operate within the applicable maximum disconnection time for the circuit and earthing arrangement.
This requires coordination between:
fault current, protective-device characteristics and Zs.
That is why selecting “a 32 A breaker” based solely on normal operating current isn't enough.
The protective device has jobs to do during both:
normal overload conditions
and
fault conditions.
Step 14 — Consider termination temperature
This one is easy to miss.
Some cable types use insulation capable of operating at higher conductor temperatures.
For example, certain thermosetting cables may be capable of operating at higher temperatures than typical equipment terminals.
But that doesn't automatically mean the entire installation can simply be designed using the cable's highest temperature rating.
Switchgear and accessories may have lower permitted terminal temperatures.
The IET has specifically highlighted this issue with XLPE/SWA applications: the designer must consider the temperature limitations of connected equipment rather than blindly selecting the highest cable temperature table. IET Wiring Regulations
Step 15 — Consider harmonics
Modern buildings contain large quantities of electronic equipment.
Examples include:
LED drivers,
IT equipment,
variable-speed drives,
UPS systems,
switch-mode power supplies.
These can introduce harmonic currents.
In three-phase systems, certain harmonics can accumulate in the neutral rather than cancel.
That means assuming:
“The neutral always carries less current than the phase conductor”
can be unsafe in some installations.
Where significant harmonic currents are expected, neutral-conductor loading and cable selection require additional consideration.
The building type and actual equipment matter.
Step 16 — Consider mechanical requirements
Sometimes the electrical calculation isn't what determines the final cable size.
Mechanical considerations can also matter.
For example:
minimum conductor sizes,
mechanical protection,
burial,
flexibility,
termination requirements,
fire performance,
support systems,
environmental exposure.
A mathematically adequate cable is not automatically an appropriate cable for the installation.
Step 17 — Consider energy efficiency
There is another side to cable sizing that is increasingly relevant.
Suppose the minimum compliant calculation allows a particular conductor.
Increasing the cable size could reduce conductor resistance.
Lower resistance means lower:
I²R losses.
That can reduce energy wasted as heat throughout the life of the installation.
The IET has highlighted that the smallest compliant conductor isn't always the most economical solution over the lifetime of a heavily loaded installation, particularly for circuits operating at substantial load for long periods. IET Wiring Regulations
This becomes particularly relevant for:
main distribution,
large sub-mains,
EV infrastructure,
data centres,
industrial loads,
continuously operated equipment.
Good design considers more than initial cable cost.
A complete worked cable-sizing example
Let's pull the process together.
We have a three-phase load:
20 kW
Supply:
400 V
Power factor:
1.0
Circuit length:
35 m
For simplicity, we'll treat it as a balanced resistive load.
Design current
Ib = 20,000 ÷ (√3 × 400)
Ib ≈ 28.9 A
Protective device
Select:
In = 32 A
Therefore:
Ib ≤ In
or:
28.9 A ≤ 32 A
Correction factors
Assume for this illustrative example only that our installation assessment establishes:
Ca = 0.94
Cg = 0.80
Combined:
0.752
Required tabulated cable capacity:
It ≥ 32 ÷ 0.752
It ≥ 42.6 A
We now select the appropriate cable table and installation reference method.
The chosen conductor must provide a tabulated capacity of at least:
42.6 A
Voltage drop
Assume the candidate cable's applicable table gives an illustrative value of:
8 mV/A/m
Voltage drop:
(8 × 28.9 × 35) ÷ 1000
= 8.1 V
Percentage:
8.1 ÷ 400 × 100
≈ 2.0%
We would then consider the rest of the distribution system to establish total voltage drop.
Fault protection
Next check:
Zs
required disconnection time
protective-device characteristic
prospective fault current
CPC thermal withstand
short-circuit withstand
Only after those checks can the cable be considered fully designed.
This is why cable-sizing software can still be wrong
Electrical-design software is extremely useful.
It can process calculations far faster than working everything manually.
But software only works with the information it receives.
Enter the wrong:
installation method,
ambient temperature,
cable grouping,
protective device,
circuit length,
fault level,
load,
and the software may produce a perfectly calculated answer to the wrong question.
The IET makes the same underlying point when discussing underground cable design: applying the correct design factors remains the responsibility of the electrical designer, even when calculation software is used. IET Wiring Regulations
Software doesn't remove the need to understand cable sizing.
It makes understanding cable sizing more valuable.
Common cable-sizing mistakes
There are several mistakes worth watching for:
Choosing a cable from the breaker size alone. A 32 A breaker does not automatically equal a particular cable CSA.
Ignoring the installation method. The same cable can have very different usable capacity depending on how it is installed.
Forgetting grouping. Multiple loaded circuits together can materially alter the thermal environment.
Ignoring thermal insulation. Insulation can significantly reduce heat dissipation.
Checking voltage drop only on the final circuit. Upstream distribution contributes to the total voltage drop too.
Using 90°C cable data without considering 70°C terminals. The entire installation needs to be compatible.
Forgetting Zs. Current-carrying capacity alone does not prove fault protection.
Trusting software without checking the inputs. A calculation is only as good as the design information behind it.
Always selecting the minimum compliant cable. Whole-life losses, future capacity and operational requirements may justify a larger conductor.
The electrical cable sizing workflow
For EDK, this is the process I'd encourage junior designers to remember:
Determine Ib → Select In → Identify cable type → Establish installation method → Apply correction factors → Determine It → Select cable → Check voltage drop → Check Zs → Check CPC → Check short-circuit withstand → Check disconnection time → Review installation and equipment conditions → Finalise cable size.
That single sequence is worth understanding properly.
Once it makes sense, cable calculations stop looking like a collection of unrelated equations.
You start seeing the circuit as a complete engineered system.
Cable sizing isn't really about cable size
This is the bigger lesson.
When somebody asks:
“What size cable do I need?”
The real engineering questions are:
What is the load?
What protective device is being used?
How is the cable installed?
What temperature will it operate in?
What other cables are beside it?
How long is the run?
What voltage drop is acceptable?
What fault current is available?
Will the protective device disconnect quickly enough?
Can the conductors survive the fault?
What equipment is connected at each end?
Once those questions have been answered, the cable size becomes the result.
Not the starting point.
Frequently Asked Questions
What is the Ib, In and Iz rule?
The fundamental relationship is:
Ib ≤ In ≤ Iz
Ib represents the circuit's design current, In the nominal current or setting of the protective device, and Iz the cable's current-carrying capacity under its installed conditions.
Can I size a cable using amps alone?
No.
Current is an important input, but cable sizing also depends on installation method, correction factors, circuit length, voltage drop, fault protection, conductor temperature and other design conditions.
Does a 32 A circuit always use the same cable size?
No.
Two 32 A circuits may require different cable sizes because they are installed differently.
A short cable clipped directly may produce a different result from a long cable grouped in containment or passing through thermal insulation.
What is the maximum voltage drop in BS 7671?
For an LV installation supplied directly from a public LV distribution system, commonly referenced BS 7671 recommendations are 3% for lighting and 5% for other uses from the origin to the load point. However, equipment requirements can demand a lower value and the recommendations should not be treated as the only consideration. IET Wiring Regulations
Should I always select the smallest compliant cable?
Not necessarily.
A larger conductor may reduce voltage drop and energy losses, provide additional capacity or better satisfy project-specific requirements. The most technically and commercially appropriate selection isn't always the smallest conductor that passes the calculation. IET Wiring Regulations
Final thoughts
Cable sizing is one of the best examples of what electrical design actually involves.
At first it looks like a calculation:
load → cable size.
In reality, it's a coordination exercise between:
the load, supply, protective device, conductor, installation environment and fault conditions.
That is why experienced electrical designers rarely answer:
“What cable size do I need?”
without first asking several more questions.
The calculation isn't about finding a number in a table.
It's about proving that the circuit will operate safely and correctly under both normal and fault conditions.
And once the cable is selected, the next piece of the design needs to record all that information correctly.
Which leads naturally into our next EDK guide:
How to Create a Distribution Board Schedule
Need practical electrical design tools?
Explore EDK cable calculation resources, distribution-board schedules, CAD symbols and professional electrical design templates built around real UK building-services workflows.
EDK technical note: This article is educational guidance rather than a substitute for the current BS 7671, manufacturer instructions, project specifications or competent electrical-design assessment. Cable ratings and correction factors should always be verified against the applicable current standards and actual installation conditions.