Electrical design in the UK is changing again.
BS 7671:2018+A4:2026 — commonly referred to as Amendment 4 of the 18th Edition Wiring Regulations — was published on 15 April 2026 and introduces a number of significant changes affecting the design, installation and verification of electrical installations.
For electrical designers, this isn't simply another book to put on the shelf.
The changes affect areas including battery storage, ICT infrastructure, Power over Ethernet and medical locations, while also incorporating previous amendments into the latest consolidated edition.
BS 7671 is the UK's national standard for low-voltage electrical installations and is relevant to new installations, additions and alterations. IET
Here's what electrical designers need to know.
What is BS 7671 Amendment 4:2026?
The full designation is:
BS 7671:2018+A4:2026 — Requirements for Electrical Installations, IET Wiring Regulations, 18th Edition.
You'll also hear it called the Orange Book.
It replaces the previous Brown Book arrangement incorporating Amendments 2 and 3.
Amendment 4 was published on 15 April 2026, with a six-month transition period. The previous edition remains valid until 15 October 2026, after which Amendment 4 becomes the edition designers and installers should be working to. IET Wiring Regulations
For anyone producing construction information now, that transition date is important.
A project designed today may not reach construction for several months. Designers therefore need to consider not only which standard is applicable when the design begins, but which edition will be relevant when the installation is actually delivered.
What has changed in Amendment 4?
Amendment 4 is a substantial update rather than a minor editorial revision.
Some of the most notable changes include:
Stationary secondary batteries
A new chapter has been introduced dealing with stationary secondary batteries used for electrical energy storage and supply.
This is particularly relevant as battery energy storage becomes increasingly common alongside solar PV, EV charging, commercial energy management and resilience systems.
For electrical designers, battery systems can no longer be treated as an unusual specialist addition. They are rapidly becoming part of mainstream electrical infrastructure.
Power over Ethernet
Amendment 4 introduces specific requirements relating to Power over Ethernet, or PoE.
Modern commercial buildings increasingly use structured cabling to power equipment such as:
wireless access points
IP cameras
access-control equipment
sensors
intelligent building devices
connected lighting equipment.
That creates additional design considerations around cable selection, current carrying capacity, heat generation, containment and coordination between electrical and data infrastructure.
Functional earthing for ICT systems
A new section covers functional earthing and functional equipotential bonding for information and communications technology equipment and systems.
Again, this reflects the increasing overlap between traditional electrical services and digital building infrastructure.
Medical locations
Section 710, covering medical locations, has received substantial revision.
Designers working on hospitals, healthcare facilities and medical environments should therefore pay particular attention to the new edition before beginning or updating designs.
These are among the principal changes identified by the IET and BSI when Amendment 4 was published. IET
What does Amendment 4 mean for electrical designers?
The important point is that electrical design isn't simply about calculating cable sizes.
An electrical designer is responsible for bringing together a complete system.
That means considering:
design current
protective-device selection
cable sizing
voltage drop
fault current
earth-fault loop impedance
thermal effects
discrimination and coordination
isolation
switching
containment
environmental conditions
equipment requirements
maintainability
installation method
future expansion.
Amendment 4 needs to be incorporated into that wider design process.
A compliant calculation sitting beside an incorrectly coordinated drawing doesn't create a good design.
Neither does a technically correct schematic that doesn't match the distribution-board schedule.
This is why drawing standards, calculation methods and document coordination matter just as much as understanding individual regulations.
Update your electrical design notes
One of the easiest areas to overlook when standards change is the drawing package itself.
Standard notes copied between projects can remain unchanged for years.
Check:
General electrical notes
Any statement referencing BS 7671 should identify the correct applicable edition.
Electrical specifications
Review references contained within electrical specifications, particularly templates reused from previous projects.
Calculation software
Check that cable-calculation and electrical-design software has been updated appropriately.
Design reports
Templates referring to previous editions should be reviewed.
Drawing legends
Any regulatory references appearing in legends or schedules should be checked.
Project specifications
Remember that project-specific specifications may impose requirements beyond the minimum provisions of BS 7671.
Don't confuse BS 7671 with legislation
This distinction is important for anyone learning electrical design.
BS 7671 is a British Standard, rather than an Act of Parliament.
However, it forms the UK's national standard for electrical installations and provides the recognised technical framework used throughout the electrical industry. IET Wiring Regulations
Other legal requirements may also apply depending on the project, including the Electricity at Work Regulations, Building Regulations and Construction (Design and Management) Regulations.
Good electrical design therefore requires more than knowing one document.
A designer needs to understand how standards, legislation, client requirements and project specifications interact.
What about existing installations?
A common misunderstanding whenever BS 7671 changes is that every older electrical installation suddenly becomes non-compliant.
That isn't the case.
The IET specifically notes that standards are not retrospective. An installation designed to a previous edition does not automatically become unsafe simply because a newer edition has been published. IET Wiring Regulations
Modifications and additions, however, need careful consideration.
The existing installation must be assessed alongside the requirements applicable to the new work.
Electrical designers should build compliance into the workflow
The best time to consider compliance isn't at the end of a project.
It's while the design is being developed.
A strong workflow might look something like this:
1. Establish the design criteria
Understand supply characteristics, building use, load requirements, resilience strategy and client requirements.
2. Develop the distribution strategy
Define major switchgear, distribution boards, sub-main routes and equipment locations.
3. Complete preliminary calculations
Determine loads, maximum demand, cable requirements and protective devices.
4. Develop coordinated layouts
Lighting, small power and specialist electrical systems need to work with architecture, structure and mechanical services.
5. Produce calculations and schedules
Layouts, schematics, distribution-board schedules and calculations should tell the same story.
6. QA the design
Check circuit references, protective devices, cable sizes, equipment loads and drawing coordination before issue.
Compliance shouldn't be added after the design.
It should be embedded within it.
Final thoughts
Amendment 4 reflects something larger happening within electrical engineering.
Buildings are becoming more electrical, more connected and more dependent on intelligent infrastructure.
Battery storage, data networks, distributed energy resources and connected equipment mean the boundary between electrical, energy and digital design is becoming increasingly blurred.
For electrical designers, keeping up with BS 7671 isn't simply about passing an exam.
It's part of producing safe, coordinated and professional construction information.